Outlines | This is Vibration/Movement Monitor, which process the data sent from the eddy current type contacting sensor or the electrokinetic type contacting vibration sensor, and show them on the meter or output to the recorder etc.. This monitor can control the abnormal value because it always observe the data. | ||||
Features | EIt suits for uncontacting vibrometer, uncontacting movement meter and contacting vibrometer. EA power supply of the sensor is built-in. EA point of contact to relay to the alarm circuit has two circuits which can be used for an alarm and a trip. (output: 1ab) EIt has an output.(4-20mA) ECombined with a Zener barrier, it compose the essentially safe explosion-protected structure. | ||||
Purposes | Contacting Vibrometer (type C) | ||||
It can measure the vibration of the bearing base by being set in the casing. | |||||
Low Frequency Contacting Vibrometer (type L) | |||||
It can measure the vibration of mil, compressor and such low turning machines. | |||||
Uncontacting Vibrometer (type N) | |||||
Set up on the metal of turning machine and you can measure the axis vibration. | |||||
Uncontacting Movement Meter (type Pj | |||||
It can measure the axis position of turning machine. | |||||
Spec | General Spec | ||||
The sort of Explosion-protected Structure | The essentially safe explosion-protected structure | ||||
Grade | 3nG5 | ||||
Attested Number | No.26988, No.26990 | ||||
Power Supply of The Driver | -16V}0.1V | ||||
Power Consumption | 30W | ||||
Weight | Approx. 3.5kg | ||||
Surrounding Temperature | 0`50 |
Code | Detector | Scale Factor | Measurable Frequency | Input Impedance |
L | Contacting Low Frequency Type | 4.8mV/100 | 1.6`10KHz | 500K |
C | Contacting Type | 10`10KHz | ||
N | Uncontacting Vibration | 0.5Vp-p/100 | ||
P | Uncontacting Displacement | 0.2V/100 |
Code | Return | Delay Time | Note |
01 | Automatic | 3 seconds | Range@Every point is set up optionally by the volume on the front panel. The Point of Contact@1ab Capacity of The Point of Contact@250V AC, 5A 125VDC 0.8A |
02 | 1 seccond | ||
03 | Manual | 3 seconds | |
04 | 1 second |
Code | Power Supply | Note |
01 | AC90`120V | 50, 60Hz |
02 | DC24V | - |
Code | Output Signal | Output ImpedanceiTolerant Resistancej | Accuracy | Linear Accuracy |
01 | 0`10mVCD | 100 | 1.0% / FS | 1.0% / FS |
02 | 0`1VCD | |||
03 | 0`5VCD | 250 | ||
04 | 4`20mA | Max load 600 | ||
05 | Isolated Type 1`5VDC | 0.25% / FS | 0.2% / FS | |
06 | Isolated Type 4`20mA |
Code | Meter Range | Note |
01 | 0`50 | Accuracy@2.5% Scale@Divided by 50 Lamps@LED |
02 | 0`100 | |
03 | 0`125 | |
04 | 0`200 | |
05 | 0`300 | |
06 | 0`500 | |
07 | -0.5`0`+0.5mm | |
08 | 0`1mm | |
09 | -1`0`+1mm | |
10 | 0`2mm |